FAA L-824 Type B Unshielded 5kV
Applications:
Airport cables are used for interconnecting the transformers and the current regulator of airfield lighting systems in series circuits, suitable for fixed applications such as taxiways, runways, navigational aids, and obstruction lighting, can be installed in conduit and direct burial.
Standards:
FAA L-824 Type B
ICEA S-96-659/NEMA WC71
Construction:
Conductor: Stranded bare or tinned copper conductor.
Insulation: EPR.
Sheath: CPE/PVC.
Technical Data:
Rated Voltage Uo/U (Um) :5kV
Maximum Conductor Temperature :90℃
Short Circuit Temperature :250℃
Operating Temperatures :-40℃~+85℃
Minimum Bending Radius :5×OD
Halogen Free :Yes
Abrasion Resistant :Yes
UV Resistant :Yes
Oil Resistant :Yes
Dimensions and Weight :
Construction | No. of Strand | Nominal Insulation Thickness | Nominal Sheath Thickness | Nominal Overall Diameter | Nominal Weight | ||||
---|---|---|---|---|---|---|---|---|---|
No. ×mm²/ AWG |
- | mm | inches | mm | inches | mm | inches | kg/km | lbs/kft |
1×6mm² | 7/19 | 2.3 | 0.09 | 1.2 | 0.05 | 10.0 | 0.39 | 150 | 101 |
1×8 | 7/19 | 2.3 | 0.09 | 0.76 | 0.03 | 10.7 | 0.420 | 180 | 121 |
1×6 | 7/19 | 2.3 | 0.09 | 0.76 | 0.03 | 11.7 | 0.460 | 238 | 160 |
1×4 | 7/19 | 2.3 | 0.09 | 0.76 | 0.03 | 12.8 | 0.505 | 326 | 219 |